Sort by:

Phoenix Double-level Terminal Block UTTB 4 3044814

PRODUCT CODE: 3044814
In stock
Phoenix Double-level Terminal Block UTTB 4 3044814
  • Number of levels: 2
  • Number of connections: 4
  • Nominal cross section: 4 mm²
  • Colour: Grey
  • Insulating material: PA
  • Flammability rating according to UL 94: V0
1 Day
£2.42

DESCRIPTION

Specifications:
  • Number of levels: 2
  • Number of connections: 4
  • Nominal cross section: 4 mm²
  • Colour: Grey
  • Insulating material: PA
  • Flammability rating according to UL 94: V0
  • Rated surge voltage: 8 kV
  • Degree of pollution: 3
  • Overvoltage category: III
  • Insulating material group: I
  • Maximum power dissipation for nominal condition: 1.02 W (the value is multiplied when connecting multiple levels)
  • Connection in acc. with standard IEC 60947-7-1
  • Nominal current IN: 30 A
  • Maximum load current: 36 A (with 6 mm² conductor cross section)
  • Nominal voltage UN: 800 V
  • Open side panel: Yes
  • Shock protection test specification: DIN EN 50274 (VDE 0660-514):2002-11
  • Back of the hand protection: guaranteed
  • Finger protection: guaranteed
  • Result of surge voltage test: Test passed
  • Result of power-frequency withstand voltage test: Test passed
  • Power frequency withstand voltage setpoint: 2 kV
  • Checking the mechanical stability of terminal points (5 x conductor connection): Test passed
  • Result of flexion and pull-out test: Test passed
  • Bending test rotation speed: 10 rpm
  • Bending test turns: 135
  • Bending test conductor cross section/weight:
  •  0.14 mm² / 0.2 kg
  • 4 mm² / 0.9 kg
  • 6 mm² / 1.4 kg
  • Result of tight fit on support: Test passed
  • Tight fit on carrier: NS 35
  • Setpoint: 1 N
  • Result of temperature-rise test: Test passed
  • Short circuit stability result: Test passed
  • Conductor cross section short circuit testing: 4 mm²
  • Short-time current: 0.48 kA
  • Ageing test for screwless modular terminal block temperature cycles: 192
  • Result of thermal test: Test passed
  • Proof of thermal characteristics (needle flame) effective duration: 30 s
  • Test specification, oscillation, broadband noise: DIN EN 50155 (VDE 0115-200):2018-05
  • Test spectrum: Service life test category 2, bogie-mounted
  • Test frequency: f1 = 5 Hz to f2 = 250 Hz
  • ASD level: 6.12 (m/s2)2/Hz
  • Acceleration: 3.12 g