Sort by:

Phoenix Ground Modular Terminal Block UT 35-PE 3044241

PRODUCT CODE: 3044241
In stock
Phoenix Ground Modular Terminal Block UT 35-PE 3044241
  • Number of levels: 1
  • Number of connections: 2
  • Nominal cross section: 35 mm²
  • Colour: green-yellow
  • Insulating material: PA
  • Flammability rating according to UL 94: V0
1 Day
£7.36

DESCRIPTION

Specifications:
  • Number of levels: 1
  • Number of connections: 2
  • Nominal cross section: 35 mm²
  • Colour: green-yellow
  • Insulating material: PA
  • Flammability rating according to UL 94: V0
  • Rated surge voltage: 8 kV
  • Degree of pollution: 3
  • Overvoltage category: III
  • Insulating material group: I
  • Open side panel: No
  • Back of the hand protection: Not guaranteed
  • Finger protection: Not guaranteed
  • Oscillation, broadband noise test result: Test passed
  • Test specification, oscillation, broadband noise: DIN EN 50155 (VDE 0115-200):2018-05
  • Test spectrum: Service life test category 2, bogie-mounted
  • Test frequency: f1 = 5 Hz to f2 = 250 Hz
  • ASD level: 6.12 (m/s2)2/Hz
  • Acceleration: 3.12 g
  • Test duration per axis: 5 h
  • Test directions: X-, Y- and Z-axis
  • Shock test result: Test passed
  • Test specification, shock test: DIN EN 50155 (VDE 0115-200):2008-03
  • Shock form: Half-sine
  • Acceleration: 30g
  • Shock duration: 18 ms
  • Number of shocks per direction: 3
  • Test directions: X-, Y- and Z-axis (pos. and neg.)
  • Relative insulation material temperature index (Elec., UL 746 B): 130 °C
  • Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)): 130 °C
  • Static insulating material application in cold: -60 °C
  • Surface flammability NFPA 130 (ASTM E 162): passed
  • Specific optical density of smoke NFPA 130 (ASTM E 662): passed
  • Calorimetric heat release NFPA 130 (ASTM E 1354): 28 MJ/kg
  • Smoke gas toxicity NFPA 130 (SMP 800C): passed